FLUKE INSULATION MULTIMETER FLU1577

$1,886.00 inc. GST

Order in

SKU: 100055457 Category: Brand:

The Fluke 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true RMS digital multimeter in a single, compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.

  • Insulation test voltages 500 V, 1000 V
  • Insulation test: 0.1 MΩ to 600 MΩ
  • Auto discharge of capacitive voltage
  • AC/DC Voltage
  • DC millivolts
  • AC/DC milliamps
  • Resistance (0.1 Ω to 50 MΩ)
  • Continuity
  • Three-year warranty
  • Remote probe, test leads, alligator clips
  • Rugged, utility hard case
  • Auto power off to save battery power
  • True RMS
  • Large display with backlight
  • Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
  • CAT III 1000V, CAT IV 600V measurement category
  • Accepts optional Fluke TPAKTM magnetic hanging system to free your hands for other work

Specifications:

  • Voltage DC:
    • Maximum voltage: 1000 V
    • Accuracy: ±(0.2%+2)
    • Maximum resolution: 0.001 V
  • Voltage AC:
  • Maximum voltage: 1000 V
    • Accuracy: ±(2%+3)
    • Maximum resolution: 0.1 mV
  • Current DC:
    • Maximum amps: 400 mA
    • Amps accuracy: ±(1.0%+2)
    • Maximum resolution: 0.01 mA
  • Current AC:
    • Maximum amps: 400 mA
    • Amps accuracy: ±(2.0%+2)
    • Maximum resolution: 0.01 mA
  • Resistance:
    • Maximum resistance: 50 MΩ
    • Accuracy: ±(1.2%+2)
    • maximum resolution: 0.1Ω
  • Minimum test current @ 1kΩ/V: 1 mA
  • Test voltages: 500, 1000 V
  • Maximum resistance per test voltage:
    • 50 V
    • 100 V
    • 250 V
    • 500 V
    • 1000 V: 600 MΩ
  • Maximum resolution per test voltage:
    • 50 V: 0.01 MΩ
    • 100 V: 0.01 MΩ
    • 250 V: 0.1 MΩ
    • 500 V:0.1 MΩ
    • 1000 V: 0.1 MΩ
  • Accuracy per test voltage:
    • 50 V: ±(3% + 5)
    • 100 V: ±(3% + 5)
    • 250 V: ±(1.5% + 5)
    • 500 V: ±(2.0% + 5)
    • 1000 V: ±(2.0% + 5)
  • Operating temperature: –20°C to +55°C
  • Storage temperature: -40°C to +60°C
  • Humidity (without condensation):
    • 0% – 95% (10°C – 30°C)
    • 0% – 75% (30°C – 40°C)
    • 0% – 40% (40°C – 55°C)
  • Operating altitude: 2000 m
  • Overvoltage category: Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V
  • Agency approvals: 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V
  • Battery life alkaline:
    • Meter use: 1000 hours
    • Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
  • IP rating: IP40
UOM

EACH

MPN FLU1577
Barcode 095969262965